|
Emergency
Lighting - 6 Monthly
Testing Procedures |
|
|
|
 |
Make sure there have been no power interruptions for 16hrs
prior to test. |
 |
Check fluoro lights for blackened ends, if found, tube and
starter is replaced. |
 |
Manual discharge test (simulated power failure) light must
stay illuminated for no less then 90 minuets. |
 |
Restore light to normal condition and check that the
battery charger operation indicator functions correctly. |
 |
Automatic discharge test. Check unit operates correctly
(visually) by the means of the indicator at each unit or indicator
panels. |
 |
Units that FAIL shall be replaced or repaired. |
 |
For indirect lighting systems, check that all reflective
surfaces around the light are in a good condition and that beam lights do
not shine in people’s eyes. |
| |
|
|
Emergency
Lighting - 12 Monthly Testing Procedures |
| |
|
 |
Carry out the above 6 monthly testing and inspection
procedures. |
 |
Clean all light emitting and reflecting surfaces. |
 |
Record all
test results and action taken. |
| |
|